Search results

1 – 2 of 2
Article
Publication date: 2 May 2017

Jacek Klucznik, Zbigniew Lubosny, Krzysztof Dobrzynski, Stanislaw Czapp, Robert Kowalak, Robert Trebski and Stanislaw Pokora

The paper aims to discuss problems of power and energy losses in a double-circuit overhead transmission line. It was observed from energy meters’ readings, that in such a line…

Abstract

Purpose

The paper aims to discuss problems of power and energy losses in a double-circuit overhead transmission line. It was observed from energy meters’ readings, that in such a line, active power losses can be measured as “negative”. The “negative” active power losses appear when the active power injected to the circuit is lower than the active power received at the circuit end. The purpose of this paper is to explain this phenomenon.

Design/methodology/approach

Theoretical considerations based on mathematical model of the transmission line of π-type confirming that effect are presented. Power losses related to series impedance of the line and to shunt admittance are calculated. The theoretical considerations are confirmed by measurements done on the real transmission line.

Findings

The calculations allow to indicate components of the active power losses, i.e. related to electromagnetic coupling among wires of a given circuit, related to electromagnetic coupling between circuits and related to shunt capacitance asymmetry. The authors indicate the influence of the line/wires geometry on the active power losses in a double-circuit overhead transmission line.

Originality/value

Explanation of the effect of “negative” active power losses’ measurement in a double-circuit overhead transmission line is provided in this paper.

Details

COMPEL - The international journal for computation and mathematics in electrical and electronic engineering, vol. 36 no. 3
Type: Research Article
ISSN: 0332-1649

Keywords

Article
Publication date: 5 May 2015

Jacek Klucznik, Zbigniew Lubosny, Krzysztof Dobrzynski and Stanislaw Czapp

The purpose of this paper is to discuss two evaluation methods of single pole auto-reclosing process effectiveness in HV transmission lines. Secondary arc current and recovery…

2355

Abstract

Purpose

The purpose of this paper is to discuss two evaluation methods of single pole auto-reclosing process effectiveness in HV transmission lines. Secondary arc current and recovery voltage results obtained by load flow calculation are compared to the results obtained by the time domain simulations. Moreover, a nonlinear secondary arc implementation is presented.

Design/methodology/approach

A computer simulation studies were performed using DIgSILENT PowerFactory® software to analyse phenomena during single phase to earth short circuit and during single pole circuit breaker opening. Possibilities of electric arc extinction for different earthing solutions of shunt reactors were examined.

Findings

The authors indicate, that precise representation of secondary electric arc in power system studies could lead to different conclusion than analysis carried out on simplified arc models. Recommendations for line construction (i.e. earthing reactor installation) and line operation (i.e. prolongation of dead time during auto-reclosing) based on time domain simulations are less restrictive than resulting from the traditional steady-state calculation approach.

Originality/value

An implementation of mathematical model of nonlinear secondary arc for DIgSILENT PowerFactory® software is presented. The model could be used during the process of design of HV transmission line, to assess its proper operation, to calculate dead time during single pole reclosing or to evaluate the necessity of installing additional earthing reactors.

Details

COMPEL: The International Journal for Computation and Mathematics in Electrical and Electronic Engineering, vol. 34 no. 3
Type: Research Article
ISSN: 0332-1649

Keywords

1 – 2 of 2