This study aims to verify whether the reduction factors for the post-fire performance of Grade 10.9 bolts stated in an earlier study at the TU Darmstadt are also valid for shear…
Abstract
Purpose
This study aims to verify whether the reduction factors for the post-fire performance of Grade 10.9 bolts stated in an earlier study at the TU Darmstadt are also valid for shear and combined tension and shear.
Design/methodology/approach
Tests on Grade 10.9 bolt sets under combined tension and shear were carried out. The tested bolts were heated and cooled without being stressed by an additional mechanical load before being tested.
Findings
The test results show that the reduction factors can also be adopted for bolts under combined tension and shear, but the tension-shear-ratio has an influence on the load bearing capacity.
Originality/value
The post-fire performance of high-strength bolts is of special interest when a building structure is evaluated after an event of fire. In contrast to conventional structural steel, high-strength bolts do not recover their original strength and material properties.