Search results

1 – 1 of 1
Article
Publication date: 1 November 2024

Fuad Baba, Jihad Awad, Yazan Elkahlout and Mohammed Sherzad

This paper aims to compare the impacts of adaptive daily and seasonal cooling setpoints on cooling energy consumption and overheating hours to determine which approach is more…

Abstract

Purpose

This paper aims to compare the impacts of adaptive daily and seasonal cooling setpoints on cooling energy consumption and overheating hours to determine which approach is more effective in a desert climate, develop a methodology that effectively integrates passive strategies with adaptive daily and seasonal cooling setpoint strategies and assess how future climate conditions will impact these strategies in the medium and long term.

Design/methodology/approach

(1) Integrate adaptive thermal comfort principles into mechanical cooling systems to find the optimized cooling setpoint. (2) Evaluating the optimized cooling setpoints using a mixed-mode operation: In this step, the natural ventilation is activated by opening 40% of the window area when the indoor temperature is higher than 23°C and the outdoor temperature. Both the adaptive seasonal and daily setpoint strategies are evaluated. (3) If overheating hours exceed acceptable limits gradually add mitigation measures (e.g. exterior shading, cool roofs and green roofs). (4) If necessary, further reduce the cooling setpoint until acceptable limits are met. (5) Generate extreme future climate scenarios and evaluate the optimized model. (6) Implement additional measures and setpoint adjustments to maintain acceptable overheating hours in future conditions.

Findings

Although the building complies with the Dubai Green Code and uses external shading, its cooling energy consumption was 92 kWh/m² in 2021 with a 24°C setpoint. Using the adaptive seasonal setpoint combined with a cool roof, night cooling and cross-ventilation reduces cooling energy consumption by 52, 48 and 35% in 2020, 2050 and 2090, respectively, with overheating hours not exceeding 40 h annually. Using an adaptive daily setpoint strategy with the same mitigation measures is similarly effective; it achieved a 57, 42 and 34% reduction in cooling energy consumption in 2020, 2050 and 2090, respectively, while eliminating overheating hours.

Originality/value

The originality and value of this study lie in optimizing cooling setpoints without the effect of overheating hours in desert climates. Using the adaptive seasonal setpoint combined with a cool roof, night cooling and cross-ventilation reduces cooling energy consumption by 52, 48 and 35% in 2020, 2050 and 2090, respectively, with overheating hours not exceeding 40 h annually. Using an adaptive daily setpoint strategy with the same mitigation measures is similarly effective; it achieved a 57, 42 and 34% reduction in cooling energy consumption in 2020, 2050 and 2090, respectively, while eliminating overheating hours.

Highlights

  • (1)

    A methodology is developed to find the optimal cooling setpoints

  • (2)

    Adaptive thermal comfort concept is extended for integration with a cooling system

  • (3)

    Validation simulation model is used using certain building information

  • (4)

    Climate change effect is studied using current and future warmer typical years

  • (5)

    Effective passive summer mitigation measures are studied

A methodology is developed to find the optimal cooling setpoints

Adaptive thermal comfort concept is extended for integration with a cooling system

Validation simulation model is used using certain building information

Climate change effect is studied using current and future warmer typical years

Effective passive summer mitigation measures are studied

Details

Smart and Sustainable Built Environment, vol. ahead-of-print no. ahead-of-print
Type: Research Article
ISSN: 2046-6099

Keywords

Access

Year

Last 3 months (1)